How to Choose Exit Sign Lights: Single-Sided vs Double-Sided

An exit sign light is the last light guiding people to an exit after a fire cuts the power. The two most common buying mistakes are fitting a single-sided light where a double-sided one belongs — so people approaching from the other side see nothing — and buying a luminaire whose emergency duration is too short, so the light goes out before everyone has evacuated. This guide explains how to choose between single- and double-sided lights, the key indicators and the acceptance points.

First, the Difference: Single-Sided Mounts on a Wall, Double-Sided Hangs or Suspends

A single-sided exit sign light has only one illuminated face and is usually wall-mounted above an exit door or on a corridor wall, for places where people only approach from one direction — for example an exit door at the end of a corridor or a stairwell entrance.

A double-sided light glows on both faces and is usually ceiling-mounted above a corridor or suspended in an open space, so people approaching from either direction can see it. Shopping mall atriums, open-plan offices and lobbies, where people may evacuate from several directions, should use double-sided lights.

Another product that is easy to confuse with exit signs is the directional sign light, whose face shows an arrow or a running figure and which is fitted in evacuation corridors to show the direction of travel. An exit sign light shows the words "EXIT" and is fitted above an exit door. The two serve different purposes — don't substitute one for the other when buying.

Key Indicators: Emergency Duration, Changeover Time, Light Source

The product standard is GB 17945-2024, Fire Emergency Lighting and Evacuation Indication System (released 29 April 2024, effective 1 May 2025, replacing GB 17945-2010), and design and installation follow GB 51309-2018, Technical Standard for Fire Emergency Lighting and Evacuation Indication System. Write the full standard numbers on purchase contracts and acceptance forms.

Emergency duration is the most important indicator. Under GB 51309-2018, the battery-powered working time of a luminaire must be at least 1.5 hours for civil buildings over 100 m tall; at least 1 hour for medical buildings, elderly care facilities, public buildings over 100,000 m² in total floor area, and underground or semi-underground buildings over 20,000 m²; and at least 0.5 hours for other buildings. Common products are rated at 90 minutes — check the rating against the building type rather than trusting the label alone.

Emergency changeover time is how long the luminaire takes to switch to emergency mode after the mains power fails. If it is too slow, the corridor goes dark in the instant the power cuts, which can cause a stampede. Ask the supplier for the measured changeover time tested under GB 17945-2024 and check it against the design requirements.

Light sources are now almost all LED. When choosing, confirm whether the luminaire is maintained or non-maintained: maintained lights stay on normally and suit places that need a permanently lit sign, such as above an exit door; non-maintained lights stay off and only light up when power fails, and are mostly used for emergency lighting luminaires. Exit sign lights are usually maintained.

Where to Install: Where People Can See Them

Fit exit sign lights above exit doors, with the bottom edge of the luminaire not too far above the top of the door frame, so people evacuating low through smoke can look up and see them. Corridor corners and stairwell entrances, where people can easily take a wrong turn, also need directional sign lights as the design requires.

There are two mounting methods: wall mounting and ceiling mounting. Single-sided lights are mostly wall-mounted; double-sided lights are mostly ceiling-mounted. For ceiling mounting, check that the rod or chain is secure and the luminaire does not swing. Nothing — shelves, billboards or decorations — may block the front of a luminaire; blocked is the same as not installed.

How to Check on Delivery: Certificates, Markings, Live Tests

Fire emergency lighting and evacuation indication products are on the compulsory product certification (CCC) list as emergency evacuation products, so they must carry a CCC certificate and a fire product identity mark (a one-item-one-code AB label). On delivery, check that the model and manufacturer on the certificate match the nameplate on the goods and that the certificate is still valid. Certificates can be checked on the Certification and Accreditation Administration's public platform (cx.cnca.cn) and the China Fire Product Information website (www.cccf.com.cn).

The luminaire should carry clear permanent markings, including the product name, model, rated voltage, emergency working time, manufacturer and production date. Be cautious of markings that are unclear or incomplete.

A live test is the simplest and most effective check: cut the mains power and see whether the luminaire switches to emergency mode within seconds and whether the light is even; then run a discharge test to confirm the emergency duration reaches the rated value. Fully charge the luminaire before testing — a half-charged battery gives a false reading.

Common Mistakes

  • Fitting a single-sided light where people approach from both sides.
  • Only checking the rated duration, not the building type it must serve.
  • Mixing up maintained and non-maintained lights.
  • Letting shelves or decorations block the luminaire.
  • Buying the wrong power-supply type — centralised power with central control suits new large buildings; self-contained battery luminaires suit small retrofits or one-off additions. Confirm which system the building already has before buying.

Frequently Asked Questions

Can a single-sided light be hung in the middle of a corridor?

Not recommended. A single-sided light has only one illuminated face — hung in the middle of a corridor, people approaching from the other side cannot see it. Corridor middles and open spaces need double-sided lights.

Should exit sign lights stay on all the time?

Maintained exit sign lights stay on normally — that is their normal working state, not wasted electricity. Non-maintained lights stay off and only light up when power fails. Don't mix the two up.

Is a 90-minute emergency duration enough?

Check the building type against GB 51309-2018: ordinary buildings need at least 0.5 hours, so 90 minutes is enough; civil buildings over 100 m tall need at least 1.5 hours, so 90 minutes is not enough. Confirm the building type before choosing.

How often should the battery be replaced?

Follow the product manual and actual discharge test results. Do a power-off test every month and a full-load discharge once a year: after 24 hours of charging, if the discharge time falls short of the rated emergency duration, or the battery leaks or bulges, replace the battery or the whole luminaire.