Warehouse Fire Equipment Checklist: By Fire Compartment
Warehouse fires are defined by concentrated combustibles, fast spread and difficult suppression. The core of warehouse fire equipment configuration is the fire compartment: get the compartments right and a fire stays inside one compartment; get them wrong and one fire burns down the whole warehouse. This guide explains warehouse fire compartments and equipment configuration.
Set the Compartments First: GB 50016-2014 Table 3.3.2
Warehouse fire compartments are based on Table 3.3.2 of GB 50016-2014 (2018 edition), Code for Fire Protection Design of Buildings. Warehouses are classed A, B, C, D and E by the fire hazard of the goods stored, from most to least hazardous, and the maximum permitted floor area of a fire compartment grows as the hazard falls.
Take the most common case, a Class C warehouse: for a single-storey warehouse with fire-resistance rating I or II, the maximum permitted floor area per fire compartment is 1,000 square metres for Class C1 and 1,500 square metres for Class C2; for a multi-storey warehouse, 700 square metres for Class C1 and 1,200 square metres for Class C2. Class B warehouses are smaller: a single-storey warehouse with fire-resistance rating I or II allows only 500 square metres per fire compartment. Class A warehouses are the smallest: a single-storey warehouse with fire-resistance rating I allows only 60 square metres per fire compartment.
Fire compartments inside a warehouse must be separated by fire walls, and in Class A and Class B warehouses the fire walls between compartments must not have doors, windows or openings. Where a warehouse or one of its fire compartments stores goods of different fire hazard classes, the hazard class of the warehouse or compartment is set by the most hazardous item. When a warehouse changes to different stored goods, the fire hazard class and fire compartments must be re-checked. Where an automatic fire extinguishing system is installed, the maximum permitted floor area of each warehouse and the maximum permitted floor area of each fire compartment may be increased by 1.0 times, except for the fire compartments of cold storage.
Extinguishers: Calculate Compartment by Compartment
Extinguisher configuration follows GB 50140-2005, Code for Design of Extinguisher Distribution in Buildings. Warehouse extinguishers must be calculated compartment by compartment — several compartments must not share one batch of extinguishers.
Ordinary goods warehouses are generally configured as medium-hazard Class A fire places: a single extinguisher must have a minimum rating of 2A, and the maximum protected area per unit rating is 75 square metres per A. Warehouses storing oil, solvents or chemicals are configured as serious hazard: a single extinguisher must have a minimum rating of 3A, and the maximum protected area per unit rating is 50 square metres per A. Each calculation unit must have at least 2 extinguishers, and each setting point should have no more than 5. The exact numbers are calculated using the formulas in GB 50140-2005, subject to the fire design documents.
Choose the extinguisher type by the fire class of the stored goods: ordinary goods take ABC dry powder extinguishers; oil and solvent storage takes ABC dry powder or foam extinguishers; alkali metals (potassium, sodium, magnesium) take Class D dry powder extinguishers — never water-type extinguishers; areas with much electrical equipment take carbon dioxide extinguishers.
Hydrant System: Hose, Nozzle and Couplings Must Be Complete
A warehouse's indoor hydrant system is the main force for fighting early-stage fires, and the equipment inside a hydrant box must be complete: fire hose, water gun, couplings and a hydrant wrench — one missing item affects use.
Fire hose follows GB 6246-2011, Fire Hose; the common size is 65 mm diameter and 20 m or 25 m length. Check hoses regularly: inspect the appearance monthly for damage or mould and check that couplings are intact; turn the hose over twice a year or swap the fold edge once a year, to prevent ageing and cracking at the folds. A used hose must be washed and dried before storage — a hose that is not dry must not be rolled up and stored.
Hydrant boxes must be placed somewhere obvious and easy to reach, the box door must not be locked, and no goods may be stacked in front of the box. Goods stacked in a warehouse must leave fire lanes clear, and the lane width and the operating space in front of hydrant boxes must meet the fire design requirements. Goods blocking hydrant boxes are the most common finding in warehouse fire inspections.
Key Areas: Electrical, Charging, Hot Work
There are three key areas for warehouse fire safety: electrical circuits, charging areas and hot-work points.
Electrical circuits: warehouse lighting fixtures must keep a safe distance from goods, electrical wiring must be protected in conduit, and no combustibles may be stacked around distribution boxes. Distribution rooms take carbon dioxide or dry powder extinguishers — water-type and foam extinguishers are strictly prohibited.
Charging areas: where a warehouse has forklift charging or EV charging, set aside a dedicated charging area, keep charging facilities a safe distance from combustibles, equip the area with ABC dry powder and carbon dioxide extinguishers, and never charge in a goods storage area.
Hot work: maintenance and welding inside a warehouse require hot-work approval; clear combustibles around the work point, keep extinguishers on site, assign a dedicated watcher, and check for smouldering after the work before leaving.
Frequently Asked Questions
How large can a warehouse fire compartment be?
It depends on the fire hazard class of the stored goods and the fire-resistance rating of the warehouse — check GB 50016-2014 Table 3.3.2. A Class C2 single-storey warehouse with fire-resistance rating I or II allows a maximum of 1,500 square metres per compartment, doubled with an automatic fire extinguishing system. Follow the fire design documents.
When different goods are stored together in a warehouse, which hazard class applies?
The most hazardous item determines it. If Class A and Class C goods share one fire compartment, the whole compartment is rated Class A.
How often should warehouse extinguishers be checked?
Under GB 50444-2008, extinguishers in yards, tank areas and similar places are checked every half month; general warehouses are checked monthly. The exact frequency depends on whether the warehouse is one of the key places listed in the code.
How often should the hose in a warehouse hydrant box be replaced?
There is no fixed service life — replace by inspection result: replace a hose promptly when it is damaged, mouldy, its lining is delaminating, or its couplings are damaged. Check the appearance monthly, and turn the hose over twice a year or swap the fold edge once a year.