Fire Equipment for EV Charging Areas: How to Set It Up

Fires in EV charging areas are defined by lithium batteries: high fire temperature, fast spread, easy reignition, and limited effect from ordinary extinguishers. Equipment for a charging area must be built around "detect early, alarm early, control the fire" — not just a few extinguishers set out. This guide explains the configuration points.

First, the Basis: Group Standards Plus Local Standards

Fire safety for e-bike charging places currently has no unified national standard; the basis is mainly the China Fire Protection Association group standard, the Fire Safety Code for Shared Electric Bicycle Charging Stations, plus local standards from provinces — for example, Shaanxi DB61/T 1748-2023, Fire Safety Code for Electric Bicycle Charging and Parking Places, and Henan DB41/T 2362-2022, Fire Safety Management Code for Electric Bicycle Parking and Charging Places. Building fire protection, fire facilities and equipment, electrical safety and use and maintenance of other e-bike charging stations may follow the group standard.

On siting: an indoor charging station should be on the ground floor, not underground or semi-underground; there should be a fire water source or outdoor hydrant within 150 metres of the site; charging is strictly prohibited in crowded places and in public lobbies, evacuation routes, stairwells, overhead floors, safety exits and other public areas of buildings, and batteries must not be taken home to charge.

Extinguishers: Medium Hazard, Class A and Class E

Under the group standard, an indoor charging station should have Class A and Class E extinguishers, configured to medium hazard. Local standards require the same: e-bike parking and charging places should have extinguishers, with the hazard class set to medium, configured per GB 50140-2005, Code for Design of Extinguisher Distribution in Buildings.

The medium-hazard Class A configuration basis: a single extinguisher must have a minimum rating of 2A, and the maximum protected area per unit rating is 75 square metres per A. Each calculation unit must have at least 2 extinguishers, and each setting point should have no more than 5. Charging areas should preferably use 9-litre or larger water-based or foam extinguishers — water cools lithium battery fires well — and dry powder extinguishers can also be fitted, the two used together.

Extinguishers should be placed at charging-area entrances and near evacuation routes, in obvious, accessible positions, with the top no higher than 1.50 metres above the floor, the bottom no lower than 0.08 metres, and extinguisher cabinets must not be locked. Check charging-area extinguishers monthly — the pressure gauge needle must be in the green zone.

Water Containers and Hydrants: Lithium Battery Fires Need Water

After a lithium battery fire, reignition is easy — even after an extinguisher puts out the flames, the battery keeps generating heat inside and may catch fire again. Under the group standard, an indoor charging station should have water containers, each with a capacity ensuring a single battery can be fully immersed, and no less than 50 litres, with a protection radius of no more than 5 metres. A burning battery can be immersed in water to cool it and prevent reignition.

Hydrant requirements: an indoor charging station should have a hydrant system; where floor area does not exceed 300 square metres, a hose reel or light-duty water tap may be used. Local standards specify further: a hose reel should have a fire hose with an internal diameter of at least 19 mm, and a light-duty water tap should have a 25 mm lined fire hose, both preferably 30 metres long, with a 6 mm equivalent-nozzle fire water gun.

Alarms, Emergency Lighting and Smoke Extraction: Early Detection Is Key

A fire alarm device is a must for a charging area: an indoor charging station should have a fire alarm device, designed, built and accepted per GB 50116, Code for Design of Automatic Fire Alarm Systems, and GB 50166, Standard for Construction and Acceptance of Fire Alarm Systems. Where the building has no fire alarm system, standalone fire alarm detectors should be fitted, with wireless alarm signals fed back to the property duty room.

Emergency lighting and evacuation signage: an indoor charging station should have emergency lighting and evacuation signage, designed, built and accepted per GB 51309, Technical Standard for Fire Emergency Lighting and Evacuation Indication Systems. Luminaires follow GB 17945-2024, with emergency duration set by building type — generally no less than 0.5 hours for ordinary buildings.

Smoke extraction: an indoor charging station should have smoke prevention and extraction facilities, preferably natural smoke extraction. A charging station whose openable window area is less than 5% of floor area should have mechanical smoke extraction. Local standards differ slightly: mechanical smoke extraction is required where effective openable window area is less than 2% of floor area. Follow the local standard when applying.

Frequently Asked Questions

Which extinguishers should an EV charging area have?

Class A and Class E extinguishers configured to medium hazard, preferably 9-litre or larger water-based or foam extinguishers, paired with ABC dry powder extinguishers. Quantities follow GB 50140-2005, with at least 2 extinguishers per calculation unit.

Must a charging area have water containers?

Under the group standard, an indoor charging station should have water containers, each with a capacity of at least 50 litres and a protection radius of no more than 5 metres. Lithium batteries easily reignite after a fire; immersion cooling is an effective way to prevent reignition.

What if a small charging area has no hydrant?

An indoor charging station with a floor area of no more than 300 square metres may use a hose reel or a light-duty water tap instead of an indoor hydrant. A light-duty water tap uses a 25 mm lined fire hose, preferably 30 metres long.

Can a charging area be set up in an underground car park?

Indoor charging stations should be on the ground floor, not underground or semi-underground. Underground charging carries high fire risk: smoke is hard to exhaust and evacuation is difficult. Existing underground charging areas should be rectified as required by the local fire and rescue authority.