Fire Extinguisher Placement: Locations & Quantities
To place fire extinguishers correctly, follow GB 50140-2005: at least 2 extinguishers per calculation unit, no more than 5 per location, in visible and accessible spots that don't block evacuation. Get the numbers, types or maintenance wrong and the premises fail inspection — or the extinguishers fail when a fire starts. This guide explains placement, type selection and inspection and maintenance under the current codes.
Placement Rules: GB 50140-2005
The code for placing fire extinguishers in buildings is GB 50140-2005, Code for Design of Extinguisher Installation in Buildings, in force since 1 October 2005 and still current. It applies to industrial and civil buildings that produce, use or store combustibles — but not to plants or warehouses producing or storing explosives, ammunition, fireworks or firecrackers.
The code sets several hard requirements:
- At least 2 extinguishers must be installed in each calculation unit.
- No more than 5 extinguishers should be placed at any one location.
- Extinguishers must be placed in visible, easily accessible locations, without blocking safe evacuation.
Quantities are calculated from the fire class and hazard level, then the protected area and extinguishing rating — have fire design professionals do the calculation to the code. The product standard for portable extinguishers is GB 4351-2005; check that purchased products comply with it.
Choosing the Type: Match the Fire Class
Fires fall into six classes: Class A (solid materials), Class B (liquids or meltable solids), Class C (gases), Class D (metals), Class E (electrical), and Class F (cooking oils and fats in cooking appliances). Different extinguishers suit different fire classes — the wrong type may not put the fire out and can even be dangerous.
- ABC dry powder extinguishers: suitable for Class A, B, C and E fires — the most common general-purpose type, used in offices, workshops and warehouses.
- CO2 extinguishers: suitable for Class B and E fires; they leave no residue after discharge, making them suitable for power distribution rooms, server rooms and precision instrument areas. Ensure ventilation when using them in confined spaces.
- Water-based extinguishers: mainly for Class A fires; never use on electrical fires.
- Fire blankets: for small fires such as kitchen oil-pan fires or clothing fires — smothering by covering. Use together with extinguishers.
- Class D metal fires and Class F kitchen fires need dedicated extinguishers — general-purpose dry powder won't work on them.
Don't place dry powder extinguishers in server rooms or archives — the powder contaminates precision equipment and documents and is hard to clean up. CO2 or clean-agent extinguishers are better for such places.
Inspection, Maintenance and Scrapping: GB 50444-2008
Ongoing management follows GB 50444-2008, Code for Acceptance and Inspection of Extinguisher Installation in Buildings:
- Routine inspection: at least once a month — every half month for crowded places and high fire-risk premises. Check the pressure gauge needle is in the green zone, the seal and safety pin are intact, the cylinder is free of corrosion and deformation, and the discharge hose is in good condition.
- Maintenance cycles: dry powder extinguishers get their first service 5 years after manufacture, then every 2 years; water-based extinguishers 3 years after manufacture, then every year; CO2 extinguishers 5 years after manufacture, then every 2 years. Use a qualified maintenance company.
- Scrapping: counted from the date of manufacture — water-based 6 years, dry powder 10 years, clean-agent 10 years, CO2 12 years. Extinguishers that reach their service life must be scrapped, even if never used.
Keep a register for every extinguisher — type, quantity, location, inspection and maintenance records and scrapping date — so everything is clear at inspection time.
Common Mistakes
- Buying without inspecting. Extinguishers left unchecked for years may already have gauges in the red zone — nothing comes out when a fire starts.
- Not scrapping expired extinguishers. Expired cylinders may be corroded and the agent may have failed — scrap them when due.
- Putting a used extinguisher back in place. Even a short discharge means the extinguisher must be sent for refilling.
Frequently Asked Questions
How many extinguishers does one office need?
Under GB 50140-2005, at least 2 extinguishers per calculation unit. The exact number is calculated from the area and fire hazard level; a small office generally needs at least 2 per floor and per fire compartment.
Dry powder or CO2 extinguishers — how do I choose?
Choose ABC dry powder for general premises — versatile and cheap. Choose CO2 for server rooms, power distribution rooms and precision instrument areas, where it leaves no residue.
Can an expired extinguisher still be used?
No. Extinguishers past their scrapping date must be scrapped — the cylinder and agent may no longer be reliable, and they will fail inspection.
Can a fire blanket replace a fire extinguisher?
No. Fire blankets suit small early-stage fires and complement extinguishers; they don't replace them.