How to Set Up Emergency Lighting and Evacuation Signage
To set up emergency lighting and evacuation signage correctly, buy luminaires certified to GB 17945-2024 with CCC certification, and design and install the system to GB 51309-2018. After a power cut in a fire, evacuation depends entirely on these lights — fitted wrong, installed wrong or unmaintained, they are as good as absent. This guide explains system types, placement and acceptance and maintenance.
Two Standards: One for Products, One for Design
Emergency lighting and evacuation signage involve two national standards:
- GB 17945-2024, Fire Emergency Lighting and Evacuation Indicating System, in force since 1 May 2025, replacing the 2010 edition — the product standard. Fire emergency luminaires are CCC (China Compulsory Certification) products; look for the CCC mark and GB 17945-2024 when purchasing.
- GB 51309-2018, Technical Standard for Fire Emergency Lighting and Evacuation Indicating System, in force since 1 March 2019 — the design, construction and acceptance standard.
Buy luminaires to GB 17945; design systems and handle acceptance to GB 51309. Keep the two standards apart.
System Types: Choose by Premises Size
- Self-contained power supply: each luminaire has its own battery and lights up automatically on power failure. Suitable for small premises, simple to install, no separate power equipment needed.
- Central power supply: a central power unit supplies all luminaires. Suitable for large premises and easier to manage centrally.
- Non-centralised control: luminaires work independently. Suitable for small premises.
- Centralised control: remote monitoring and fault alarms. Recommended for large buildings and crowded places; some systems support dynamic evacuation guidance, adjusting the indicated direction according to the fire situation.
Placement Essentials
Evacuation corridors, stairwells and safety exits all need emergency lighting and evacuation signage. Mount exit signs above exits and directional signs low on corridor walls or on the floor — never blocked by shelves or decorations — with the indicated direction matching the evacuation route. A sign pointing the wrong way is more dangerous than no sign at all.
Rooms that must keep working during a fire — fire control rooms, pump rooms, power distribution rooms and smoke control equipment rooms — need backup lighting.
Key Indicators
- Emergency switch-on time: no more than 0.25 seconds in high-risk premises, no more than 5 seconds elsewhere. The lights must come on immediately after a power cut — no waiting.
- Duration: under GB 51309-2018, at least 1.5 hours for residential buildings over 100 m high; at least 1.0 hour for medical buildings, elderly care facilities, public buildings with a total floor area over 100,000 m², and underground or semi-underground buildings over 20,000 m²; at least 0.5 hours for other buildings. Check the battery capacity is sufficient when purchasing.
- Evacuation lighting illuminance: the minimum horizontal illuminance on evacuation corridor floors must be at least 1.0 lx, and at least 3.0 lx in crowded places. Stairwells, lobbies and other areas have higher requirements — follow the design code for the values.
Acceptance and Maintenance
At acceptance, check the CCC certificates, test reports and product markings — standard numbers and models on the certificates must match the actual products. After commissioning, inspect and test regularly, and replace luminaires that don't light or batteries that have aged promptly, following GB 51309-2018 and the product manuals for the intervals.
Common Mistakes
- Using ordinary luminaires instead of fire emergency luminaires. Ordinary luminaires go out when the power fails — they have no emergency function.
- Installing without inspecting. Aged batteries mean the lights won't come on in a power cut — as good as not installed.
- Blocked indicator lights. Shelves and decorations hiding evacuation signs mean people can't find the exits.
- Indicators pointing the wrong way. Signs pointing to a dead end are more dangerous than no signs.
- Insufficient emergency duration. Batteries with too little capacity, or aged batteries, mean the lights go out before evacuation is complete.
Frequently Asked Questions
How are emergency lights different from ordinary rechargeable lights?
Fire emergency luminaires are CCC-certified products made to GB 17945. They switch to battery power automatically after a power cut and light up within 5 seconds, with standard requirements for duration and illuminance. Ordinary rechargeable lights cannot replace them.
How high should evacuation indicator lights be mounted?
Exit signs go above exits; directional signs go low on corridor walls or on the floor. Follow GB 51309-2018 for the exact heights at design time, and never let them be blocked.
Does emergency lighting need a backup power supply?
Fire emergency lighting is itself a backup power system — luminaires have built-in batteries or are fed by a central power unit. The key is that battery capacity must be sufficient and duration must meet the code requirements.
Do retrofits of old buildings need luminaires to the 2024 standard?
After GB 17945-2024 took effect, newly certified products follow the new standard. For retrofits and replacements in old buildings, buy to the new standard; follow local fire acceptance requirements in detail.