How Often Should a Combustible Gas Alarm Be Calibrated?

A combustible gas alarm is verified at least once a year: under JJG 693-2011, Verification Regulation for Combustible Gas Detectors and Alarms, the verification period is generally no more than one year. High-risk premises can shorten it to six months. Using an alarm past its verification expiry means its readings may have drifted without anyone knowing — the same as having no alarm at all.

Once a Year Is the Floor, Not a Suggestion

  • Clause 5.5 of JJG 693-2011 states that the verification period for combustible gas detectors and alarms is generally no more than one year.
  • If the readings are in doubt, a main part has been replaced, or the unit has been repaired, send it for verification promptly — do not wait for the next cycle.
  • Verification bodies: send the unit to a qualified metrology verification body or to the manufacturer's after-sales verification service, and file the verification certificate in a register.
  • Sensors are consumables: their service life is generally 2–5 years, and the unit must be verified again after a sensor is replaced.

What Verification Checks

  • Indication error: standard gas of a known concentration is fed in, and the alarm's reading is checked against the standard value within the permitted error.
  • Alarm function: the level-1 alarm is set no higher than 25% LEL and the level-2 alarm no higher than 50% LEL, under GB/T 50493-2019.
  • Response time: whether the alarm responds promptly after gas is applied. A slow response means repair or a sensor replacement.
  • Appearance and installation: whether the probe's dust cover is blocked, whether the mounting position is obstructed, and whether the wiring is intact.

Routine Maintenance

  • Press the test button once a month to check the alarm function — a lit lamp alone is not enough; confirm the audible and visible alarms both work.
  • Clean the probe dust cover every quarter, more often in greasy kitchens and workshops.
  • Keep a register: record each detector's model, position, commissioning date, verification expiry and replacement history, and arrange verification before expiry.
  • Overdue verification, no register, or an obstructed probe all count as real defects in fire facility inspection.

Frequently Asked Questions

How often should a combustible gas alarm be calibrated?

The verification period is generally no more than one year under JJG 693-2011 — at least once a year. High-risk premises can shorten it to six months.

How should the alarm values be set?

Under GB/T 50493-2019, the level-1 alarm is set no higher than 25% LEL and the level-2 alarm no higher than 50% LEL. Too low means frequent false alarms; too high means the warning comes too late.

When should an alarm be sent for early verification?

Whenever the readings are in doubt, the unit has suffered abnormal vibration, a main part has been replaced, or it has been repaired. Do not wait for the next scheduled cycle.

Is pressing the test button each day enough?

No. The test button only checks the alarm circuit — whether the readings are accurate needs a standard gas check. Monthly button tests, quarterly probe cleaning and yearly verification are all required.