Fire Extinguisher Inspection & Scrapping Rules

"Annual inspection" for fire extinguishers is a loose term — strictly speaking, China has no unified annual inspection system for extinguishers. The real requirements are three things: a monthly check, service when due, and scrapping at the end of service life. This article sets out the dates and the basis, so a unit can keep its extinguishers on the compliant side of the line.

Monthly Check: What to Look At, and Who Checks

Under GB 50444-2008, Code for Acceptance and Inspection of Extinguisher Distribution in Buildings, the configuration, appearance and similar items of extinguishers must be checked at least once a month. The check can be done by the unit's own technical staff — there is no need to call in an outside body every time.

A monthly check covers: whether the extinguisher is in its original place and easy to reach; whether the pressure gauge needle is in the green zone; whether the lead seal and safety pin are intact; whether the cylinder shows obvious rust, deformation or damage; whether the hose and nozzle are blocked; and whether the nameplate is legible. A carbon dioxide extinguisher has no pressure gauge, so the check focuses on the lead seal and appearance, with weighing checks on a separate cycle.

Keep a record of the check — date, inspector and any problems found. In a fire inspection, that record is the evidence that the unit's day-to-day management is in order. For how to read the gauge, see How to Read a Fire Extinguisher Pressure Gauge.

Service When Due: First Service at 5 Years, Then Every 2 Years

An extinguisher must be serviced when its service date arrives, even if it has never been used. Under Table 5.3.2 of GB 50444-2008: a water-based extinguisher gets its first service 3 years after leaving the factory, then once every year; a dry powder, clean-gas or carbon dioxide extinguisher gets its first service 5 years after leaving the factory, then once every 2 years.

Service must be done by the extinguisher manufacturer or a professional service provider, following GA 95-2015, Extinguisher Maintenance. A unit must not open the cylinder and change the agent itself. If there is mechanical damage, obvious rust, agent leakage or the extinguisher has been opened and used, send it for service at once — do not wait for the due date.

Note that after GB 55036-2022, General Code for Fire Protection Facilities, came into force on 1 March 2023, the mandatory clauses of GB 50444-2008 on service intervals were abolished, replaced by the general rule that "extinguishers shall be maintained, serviced and scrapped regularly". In practice, however, many local fire departments still judge by the old intervals when inspecting, so following that schedule for service is the safest course — follow the requirements of the local fire and rescue authority in each case.

Scrapping at the End of Service Life: Dry Powder 10 Years, CO2 12 Years

Counted from the extinguisher's factory date, an extinguisher must be scrapped when it reaches the following ages, even if it has never been used and still looks new: water-based extinguishers 6 years, dry powder extinguishers 10 years, clean-gas extinguishers 10 years, carbon dioxide extinguishers and gas cylinders 12 years. The factory date is stamped on the cylinder.

The scrapping age is a hard red line — servicing, refilling or replacing parts cannot reset it. An over-age extinguisher in use counts as a substandard fire product, and putting it into service violates the relevant provisions of the Fire Protection Law. After scrapping, replace it on an equivalent-substitution basis — do not leave the spot empty.

Scrap also in these cases: severe cylinder rust or deformation, cracks in the cylinder or head, an extinguisher that has been through a fire, and any other case that GB 50444-2008 and GA 95-2015 say should be scrapped.

Work the Service Life Out at Purchase Time

When buying an extinguisher, check the factory date stamped on the cylinder — do not buy "new" stock that has sat in storage for years. A dry powder extinguisher is scrapped at 10 years, so one bought after 3 years in storage has only 7 years of use left. For bulk purchases, ask the supplier for recently manufactured products and write the production-date requirement into the contract.

Also note that the dry powder agent itself ages — it is generally considered to need replacing every 5 to 6 years, following the product instructions and the service provider's test results. Agent replacement and the cylinder hydraulic test are the service provider's work; at acceptance, the unit only needs to check the service record. For how to work out how many extinguishers a place needs, see How to Configure Fire Extinguishers: Place, Quantity and Inspection.

Frequently Asked Questions

Do fire extinguishers really need an annual inspection?

There is no unified national 'annual inspection' system. Day-to-day management is a monthly check, service when due, and scrapping at the end of service life. Some localities or industries have their own inspection requirements — follow the local fire and rescue authority.

Must a dry powder extinguisher be serviced 5 years after leaving the factory?

Yes. Even if it has never been used and the pressure gauge reads normal, it must go to a professional service provider at 5 years, then every 2 years after that. Only watching the gauge misses internal cylinder rust and caked agent.

How should a scrapped fire extinguisher be handled?

A scrapped extinguisher should be collected and handled by the manufacturer or a professional service provider — never dismantle the residual agent or pressure yourself. Replace it on an equivalent-substitution basis at once, so there is no gap in coverage.

A new extinguisher's gauge is in the green zone — does it still need checking?

Yes. A monthly check is not only about the gauge: it also covers position, lead seal, cylinder, hose and nozzle. An extinguisher moved away, blocked by clutter or with a blocked hose will still show green on the gauge.