Company Fire Equipment Checklist by Area
The most common mistake in company fire equipment is fitting the whole company with one kind of extinguisher to one standard. Offices, production workshops, warehouses and electrical rooms have completely different fire classes and risk levels, so the way they are equipped should differ too. This article explains company fire equipment by place.
First Set the Basis: GB 50140-2005
The main basis for a company configuring extinguishers is GB 50140-2005, Code for Design of Extinguisher Distribution in Buildings, in force from 1 October 2005. The code's core logic is: first set the place's fire class and risk level, then set the extinguisher type, size and quantity.
Fire classes follow GB/T 4968-2008, Classification of Fires, which divides fires into six classes, A, B, C, D, E and F: Class A is solid-material fires, Class B is liquid or meltable-solid fires, Class C is gas fires, Class D is metal fires, Class E is fires involving live electrical equipment, and Class F is fires in cooking appliances involving cooking oil. The most common in companies are Class A (paper, wood, packaging), Class B (oils, solvents) and Class E (electrical equipment).
Risk levels are divided into three grades: serious, medium and light. The minimum configuration benchmarks for Class A fire places are: serious risk — minimum single-extinguisher rating 3A, maximum protected area per unit rating 50 m²/A; medium risk — 2A and 75 m²/A; light risk — 1A and 100 m²/A. For Class B fire places: serious risk — 89B and 0.5 m²/B; medium risk — 55B and 1.0 m²/B; light risk — 21B and 1.5 m²/B.
Two hard rules to remember: a calculation unit must have no fewer than 2 extinguishers, and a single setting point should have no more than 5 extinguishers.
Office Area: Light Risk, ABC Dry Powder as the Main Type
Offices, meeting rooms and archive rooms are light-risk Class A fire places, and ABC dry powder extinguishers cover them. A 4 kg ABC dry powder portable extinguisher is the common choice, with a rating generally around 2A.
Setting requirements: extinguishers should be placed in obvious, easily reached spots that do not block safe evacuation; they should sit in extinguisher cabinets or on hooks or brackets, with the top no more than 1.50 m above the floor and the bottom no less than 0.08 m above the floor; and extinguisher cabinets must not be locked. Archive rooms and server rooms need separate thought: archive rooms fear water and powder contamination, so carbon dioxide or clean-gas extinguishers suit them; server rooms are Class E fire places, equipped with ammonium phosphate dry powder or carbon dioxide extinguishers. For how to read the gauge, see How to Read a Fire Extinguisher Pressure Gauge.
Production Workshop: Type by Process
Workshop configuration depends on the production process and what is stored. A machining workshop with cutting oil and lubricants is a Class B fire place, equipped with ABC dry powder or foam extinguishers; a spray-painting workshop with paint and solvents is serious risk, with extinguisher numbers worked out to the serious-risk benchmark; welding areas need extinguishers and fire blankets, since welding slag igniting combustibles is the most common workshop fire cause.
Workshops also need the supporting equipment for the hydrant system: fire hoses, nozzles and couplings must be complete, with the contents of hydrant cabinets checked monthly and missing items replaced promptly. A large workshop with many staff should set up a mini fire station, centrally storing extinguishers, hoses, nozzles, fire suits, helmets, torches and other equipment, so a starting fire can be reached quickly.
Warehouse and Electrical Room: Key Places Get Key Equipment
Warehouse configuration follows the fire risk category of what is stored. An ordinary goods warehouse is medium risk, equipped with ABC dry powder extinguishers; a warehouse storing oils or chemicals is serious risk, with extinguisher numbers and sizes raised, and types chosen by the fire class of what is stored.
Electrical rooms and transformer rooms are Class E fire places, equipped with carbon dioxide or dry powder extinguishers — never water-type or foam extinguishers. Hang a "No Smoking or Open Flames" sign at the electrical room door, and store no combustible clutter inside. A canteen kitchen is a Class F fire place: oil-pan fires must not be doused with water, so equip it with a fire blanket and an ABC dry powder extinguisher. For kitchen fire practice, see Kitchen Fire: Extinguisher and Fire Blanket Together.
Configuration Checklist Summary
A complete company fire equipment list should include at least these categories:
- Extinguishers: by place, fire class and risk level, ABC dry powder as the main type, with carbon dioxide and water-based types for special places.
- Hydrant supporting equipment: fire hoses, nozzles, couplings and hydrant wrenches.
- Evacuation and escape equipment: exit signs, emergency lighting, filtering self-rescue respirators and emergency torches.
- Personal protective equipment: fire suits, fire helmets, gloves and protective boots, issued to volunteer firefighters and mini fire stations.
- Alarm equipment: manual alarm buttons, megaphones and alarm bells.
Frequently Asked Questions
How do I work out how many extinguishers a company needs?
Use the GB 50140-2005 formula: the minimum total rating for a calculation unit is Q = K x S / U, where S is the protected area, U is the maximum protected area per unit rating, and K is a correction factor. Divide the total rating by one extinguisher's rating to get the number. A calculation unit needs at least 2 extinguishers.
Can a whole company use only ABC dry powder extinguishers?
Most places can, but server rooms, archive rooms, electrical rooms and kitchens need their own types. Server rooms and electrical rooms use carbon dioxide extinguishers, kitchens add fire blankets, and archive rooms use carbon dioxide or clean-gas extinguishers.
Can an extinguisher cabinet be locked?
No. GB 50140-2005 states plainly that extinguisher cabinets must not be locked — a cabinet that cannot be opened in a fire is the same as having no extinguisher.
Must a company build a mini fire station?
Key fire-safety units should build one; other units can build one voluntarily by scale and risk. If one is built, its equipment must be complete, its staff trained, and drills held regularly — it must not be just a sign on the wall.