Electrical PPE Checklist: Insulating Protection by Voltage
Electrical PPE is chosen by voltage: insulating gloves and shoes must be rated above the working voltage — one class too low is the same as no protection. Insulating gloves run from Class 00 to Class 4 under GB/T 17622-2008, with maximum working AC voltages from 500 V to 36,000 V; insulating shoes are chosen by their marked voltage rating, with 6 kV and 12 kV the common ratings.
How Are Insulating Glove Classes Divided?
The current Chinese standard for insulating gloves is GB/T 17622-2008, Insulating Gloves for Live Working, identical to IEC 60903. It divides gloves into six classes by maximum working voltage: Class 00, 500 V AC, for low-voltage distribution; Class 0, 1,000 V, for low-voltage line maintenance; Class 1, 7,500 V, for 10 kV distribution lines; Class 2, 17,000 V, for 35 kV substations; Class 3, 26,500 V, for high-voltage transmission lines; Class 4, 36,000 V, for extra-high-voltage work.
The iron rule: the glove's maximum working voltage must be above the site voltage. Choose the matching class or higher — never a lower class to save money. Glove color has nothing to do with the class; read the class marking on the glove. Insulating gloves are not currently stocked on this site, so buy them separately.
How Do I Choose Between 6 kV and 12 kV Insulating Shoes?
Choose insulating safety shoes by the voltage marked on them: the Honeywell BC0919702E ECO 6 kV shoe suits work at 6 kV and below, while the Delta Plus 301234 RIMINI 12 kV shoe and the Honeywell 702 electrician shoe suit higher-voltage work. Confirm the site voltage first — the marked rating must be above it.
Hand and foot insulation go together: gloves without insulating shoes leave the protection incomplete. See Safety Shoes Buying Guide: Impact & Puncture Standards for shoe selection basics.
How Often Must Insulating PPE Be Tested?
Under DL/T 976-2017, Preventive Test Code for Live Working Tools, Devices and Equipment, the preventive test cycle for insulating gloves is 6 months. Tests are usually AC withstand-voltage tests; a glove that fails is retired at once and never used again. Insulating shoes need periodic testing too, on the cycle set by the product instructions and company rules.
On top of scheduled tests, check before each use: look for damage, cracks, holes or sticky ageing, then roll up the cuff, inflate the glove and check for leaks. Any damage or leak means stop using it at once. Keep a register — number each pair of gloves and record the purchase date, test date and next test date. Gloves past their test date must not be used, because insulation decay cannot be seen from the outside; only a test proves it.
What Else Does Electrical Work Need Besides Gloves and Shoes?
- Head protection: safety helmets under GB 2811-2019. See How to Choose a Safety Helmet: GB 2811 Explained.
- Eye and face protection: goggles against arc flash and flying objects, worn for climbing and maintenance work.
- Body protection: workwear issued by job role; substations and other sites with arc-flash requirements need arc-flash suits under company rules (not currently stocked on this site).
- Insulating mats and platforms: auxiliary insulation for live work, not currently stocked on this site — buy them separately.
What Should Delivery Acceptance Check?
Check four things on delivery: the standard number on the packaging (GB/T 17622-2008 for insulating gloves), whether the model and manufacturer on the test report match the goods, whether the LA mark is complete, and whether the glove class marking is clear. Reject goods with an expired report or a report that does not match the goods. Issue PPE by job role and keep issue records. See How to Choose Work Gloves: A Matching Guide by Trade for glove matching by trade.
Common Mistakes
- Choosing a glove class too low to save money. A voltage above the glove's maximum working voltage will break it down.
- Wearing gloves but no insulating shoes. Hand and foot insulation go together — one without the other leaves the protection incomplete.
- Using ordinary rubber gloves as insulating gloves. They have never passed electrical performance tests, so their insulation is not guaranteed and they cannot be used for live work.
- Buying gloves and never testing them. Rubber ageing and pinholes cannot be seen from the outside — a glove past its test date must not be used even if it looks fine.
Frequently Asked Questions
What should electrical work stock first?
Set the insulation class by the working voltage first: insulating gloves and shoes must be rated above it — one class too low is the same as no protection. Then stock head, eye and face, and body protection to complete the set.
How often must insulating gloves be tested?
Under DL/T 976-2017, the preventive test cycle is 6 months. Before each use, also do a visual check and an air test — stop using a glove at once if it is damaged or leaking, and never use one past its test date even if it looks fine.
How do I choose between 6 kV and 12 kV insulating shoes?
Choose by the working voltage: the voltage marked on the shoe must be above it. 6 kV suits work at 6 kV and below; 12 kV suits higher-voltage work. Confirm the site voltage before ordering.
Can an insulating glove with a small hole still be used?
No. Any damage, hole or crack destroys the insulation and creates a shock risk. Retire a damaged glove at once — never patch it and keep using it.