Fire Equipment Checks: Monthly & Quarterly Lists
Buying fire equipment is only the first step. Without checks, an extinguisher sits undercharged, a hose goes mouldy and an emergency light's battery ages — and not one of them works when a fire breaks out. Checks must follow frequency, items and records, not feeling. This article lists the monthly, quarterly and annual inspection items.
Inspection Frequencies: Patrol, Monthly, Quarterly and Annual
Fire equipment inspection has four levels, based mainly on GB 50444-2008, Code for Acceptance and Inspection of Extinguisher Distribution in Buildings, and GB 25201-2010, Maintenance and Management of Building Fire Protection Facilities.
A patrol check is a daily visual check: under GB 25201-2010, key fire-safety units must patrol at least once a day, and other units at least once a week. A monthly check is a full check: under GB 50444-2008, an extinguisher's configuration, appearance and similar items must be checked once a month; extinguishers in waiting rooms (for trains, planes and ships), song-and-dance entertainment and video-game venues and other crowded public places, as well as yards, tank areas, petrochemical installations, petrol stations, boiler rooms, basements and similar places, are checked every half month. A quarterly check is a functional test — for example starting the fire pump, testing emergency-lighting power switching and testing hydrant discharge pressure. An annual check is a full test: at least once a year, the building's fire facilities must be fully tested by a qualified fire technical service body. Under GB 25201-2010, a sample of the same batch of extinguishers must be drawn each year for fire-extinguishing and discharge performance tests.
Monthly Checklist: Extinguishers, Hydrants, Emergency Lights
The monthly check is the core of day-to-day inspection, done once a month:
- Extinguishers: check that the configured quantity is complete and the position is not blocked or moved; check that the pressure-gauge needle is in the green zone, and weigh carbon dioxide extinguishers to check leakage; check the cylinder for rust, deformation or damage; check that the safety pin, nozzle and hose are intact; and check the service certificate and production date, putting extinguishers near their scrapping date on the replacement list in advance.
- Hydrants: check that the hydrant cabinet contains the hose, nozzle, coupling and wrench; check the hose for damage or mould; check that the cabinet door opens normally and the cabinet is undamaged; and check the hydrant valve for rust or leakage.
- Emergency lighting and evacuation signs: test the power-switching function once a month — cut the main power and see whether the lights switch to emergency mode with normal brightness; check the lights for damage and legible markings; and check that nothing blocks the lights.
Every monthly check must be recorded: the date, the inspector, the results, the problems found and how they were handled. Keep the records on file for inspection. For the full service and scrapping timeline, see Fire Equipment Acceptance: Checking 3C Certificates.
Quarterly Checklist: Functional Tests Must Not Be Skipped
The quarterly check is done once a quarter and focuses on functional tests, not just appearance:
- Fire pump: start it once a quarter and check that it starts normally, discharges normally and runs without abnormal noise. A fire pump left unused for a long time easily seizes with rust, so regular starting is necessary maintenance.
- Hydrant system: test discharge pressure once a quarter — open the hydrant at the most unfavourable point and check that the nozzle's solid water jet meets the requirement. When testing, take care with drainage and do not discharge test water somewhere that fears water.
- Emergency lighting and evacuation signs: check illuminance once a quarter — illuminance at key spots such as stairwells and front rooms must meet the requirement; and check the central power supply's batteries, replacing any that have reached the end of their service life.
Annual Check and Service or Scrapping: Deal with Due Items
Extinguisher service and scrapping follow GA 95-2015, Extinguisher Maintenance (now numbered XF 95-2015). Scrapping ages, counted from the factory date: water-based extinguishers 6 years, dry powder extinguishers 10 years, clean-gas extinguishers 10 years, carbon dioxide extinguishers and gas cylinders 12 years. An extinguisher that has reached its scrapping age must be scrapped even if it has never been used — service and refilling cannot reset the scrapping age.
Service intervals follow Table 5.3.2 of GB 50444-2008: a water-based extinguisher gets its first service 3 years after leaving the factory, then once every year; a dry powder or carbon dioxide extinguisher gets its first service 5 years after leaving the factory, then once every 2 years. Extinguishers needing service or scrapping must be handled by the extinguisher manufacturer or a professional service provider — a unit must not dismantle them itself.
After scrapping, replace on an equivalent-substitution basis, under Article 10.0.7 of GB 55036-2022, General Code for Fire Protection Facilities. Do not throw a scrapped extinguisher away casually — the service body should provide a scrapping and recovery service. For the company equipment list by area, see Company Fire Equipment Checklist by Area, and for building a mini fire station, see How to Build a Mini Fire Station: Equipment Checklist.
Frequently Asked Questions
What is the difference between a patrol check and a monthly check?
A patrol check is a daily visual check — is the equipment there, is it blocked. Key fire-safety units patrol at least once a day, other units at least once a week. A monthly check is a full check of configuration, appearance, pressure gauges and other specific items, done once a month. Both are required and cannot replace each other.
A check finds an extinguisher gauge needle in the red zone — what now?
Stop using it at once, send it to a service provider for refilling or replacement, and put an equivalent substitute extinguisher in its place so there is no gap in coverage. Record the problem and how it was handled.
Must a professional body do the quarterly check?
A unit can do the quarterly functional tests itself — for example starting the fire pump and testing hydrant discharge pressure. The annual full test must be entrusted to a qualified fire technical service body. For items a unit cannot do itself, ask a professional body to help.
How long must inspection records be kept?
Inspection records are part of the fire safety management archive and must be kept on file long-term for inspection. Fire supervision checks will sample inspection records, and missing records are treated as a failure to carry out fire safety duties.