How to Choose Emergency Lights: Twin-Head vs Exit Signs
An emergency light is the signpost in a power-cut fire: when the mains power fails it switches automatically to its battery, lighting the evacuation route and showing the way to the safety exit. It comes in two main kinds — emergency lighting lights the way, most commonly a twin-head light; evacuation indicator lights show the direction, most commonly a safety exit sign. Their selection points are different.
The Standard First: GB 17945-2024 Is the Current Version
The product standard for fire emergency lighting and evacuation indicator systems is GB 17945-2024, Fire Emergency Lighting and Evacuation Indication Systems, published on 29 April 2024 and in force from 1 May 2025, replacing GB 17945-2010. When buying, look for the 2024 version — a certificate to the 2010 version does not pass a project that requires the 2024 version.
The boundaries of three standards must be kept clear: GB 17945 covers products — whether the lights, controllers and central power supplies themselves are compliant is judged by this standard; GB 51309-2018, Technical Standard for Fire Emergency Lighting and Evacuation Indication Systems, covers design, construction and acceptance — how the system is powered and how circuits are divided is judged by this standard; GB 55037-2022, General Code for Fire Protection of Buildings, sets the bottom line and is a fully mandatory standard. Buy products against GB 17945, and design and accept works against GB 51309.
Fire emergency lights are compulsory-certification products. When buying, check the CCC certificate — the standard applied on the certificate should read GB 17945-2024, and the model and producer must match the product.
Twin-Head Emergency Lights: Lighting the Way
A twin-head emergency light has two lamp heads with adjustable angles. Normally it runs on mains power and charges its battery; when the mains fails it switches automatically to battery power, and the two heads light the evacuation route and stairwell. It is generally installed in evacuation corridors, stairwells, front rooms and above evacuation exits.
Buying points: the emergency duration must be at least 90 minutes — the most basic indicator, keeping the light on for more than 90 minutes after a power cut; emergency start-up must be fast, lighting automatically within seconds of the power failing; the lamp heads must be angle-adjustable, so they can be aimed at the area that needs light after installation; and the battery type must meet the new standard — lithium iron phosphate batteries are now mainstream.
The new GB 17945-2024 sets higher requirements for lights, including emergency luminous efficacy, self-test functions and protection ratings. When buying, read the test report and check the key indicators: luminous efficacy, duration and start-up time.
Evacuation Indicator Lights: Showing the Direction
Evacuation indicator lights include safety exit signs and evacuation direction signs. A safety exit sign sits above the safety exit and reads "safety exit"; an evacuation direction sign sits on the floor or lower wall of the evacuation corridor, with an arrow showing the evacuation direction.
Selection points for sign lights: the sign must be clear — the text and arrow must be clearly visible with the power cut; the installation height must meet requirements — a safety exit sign must be at least 2 m above the floor, and must not be hidden by the door; evacuation direction signs must be installed in the correct evacuation direction, with arrows pointing the right way.
Sign lights come in single-sided and double-sided types: single-sided mounts on a wall, double-sided hangs in the middle of a corridor. There is also a combined lighting-and-sign light that puts emergency lighting and evacuation indication in one fitting, suited to places with limited space. Buy the type on the design drawings — do not change the type yourself. For the full configuration rules, see our guide on emergency lighting and evacuation signs and how to choose exit signs.
Self-Test: A Hard Requirement of the New Version
GB 17945-2024 sets clear requirements for system self-tests: the system should carry out an emergency start-up function check and a self-test duration check once a month and once a quarter; the monthly self-test lasts 300 to 600 seconds, and the quarterly self-test lasts 30 minutes plus or minus 5 minutes.
A self-test means the light regularly checks itself and raises an alarm automatically when it finds a fault. When buying, confirm the light has a self-test function, and find out how self-test results are viewed and how faults are alarmed. An old-model light without self-test can fail silently — and finding out it does not light during a power cut is too late.
Installation and Maintenance: Right Place, Regular Tests
Install in the positions on the GB 51309-2018 design drawings — do not change them at will. Emergency lights go in evacuation routes, stairwells and safety exits; evacuation indicator lights go above safety exits and along evacuation corridors. A light installed in the wrong place is the same as no light at all, and will fail acceptance.
Daily maintenance: check once a month that lights are intact and signs are normal; run an emergency start-up test once a quarter — cut the power and check that lights come on normally and the duration meets the requirement; do a full check once a year, and replace ageing batteries with insufficient capacity promptly. The battery is the part of an emergency light most likely to fail — replace it when due, do not wait for a power cut to discover the battery is dead.
Frequently Asked Questions
What is the difference between a twin-head light and a sign light?
A twin-head light is an emergency lighting light that lights the evacuation route; a sign light is an evacuation indicator light that shows safety exits and evacuation directions. They do different jobs and neither can be left out — configure them as a set, following the design drawings.
How long does an emergency light stay on after a power cut?
The emergency duration must be at least 90 minutes. When buying, check the measured duration on the test report — below 90 minutes is not acceptable. As the battery ages the duration shortens, so test regularly and replace the battery in time.
Can lights made to GB 17945-2010 still be used?
Lights already installed to the old standard can continue in use, but new purchases and new projects must follow GB 17945-2024. When an old-standard product certificate expires it must be renewed under the new version, and old-standard stock should not be bought any more.
Is it normal for an emergency light to stay off in normal times?
Yes, for a non-maintained emergency light — it stays off normally and lights only after a power cut. A maintained emergency light stays on normally and keeps lighting after a power cut. Both working modes are acceptable, depending on the design. Staying off normally does not mean it is broken — lighting in a power-cut test is what matters.