Shopping Mall Fire Equipment Checklist by Area
A shopping mall is a typical key fire-safety unit: crowded, open long hours, full of combustible goods and complex electrical wiring. Once a fire starts, evacuation is hard and losses are heavy. Mall fire equipment must do more than merely exist — it must be fitted place by place, key area by key area. This article explains the configuration priorities for each part of a mall.
First Set the Tone: A Mall Is a Key Fire-Safety Unit
Under the Regulations on Fire Safety Management of State Organs, Organisations, Enterprises and Institutions, a shopping mall is a key fire-safety unit, managed more strictly than an ordinary unit: daily fire patrols, with patrols in public gathering places at least once every two hours during business hours; fire-fighting and emergency evacuation drills at least once every half year; and extinguisher checks every half month, rather than once a month.
Extinguisher configuration follows GB 50140-2005, Code for Design of Extinguisher Distribution in Buildings. A mall sales floor is generally configured as a medium-risk Class A fire place, with a minimum single-extinguisher rating of 2A and a maximum protected area per unit rating of 75 m²/A. A calculation unit must have at least 2 extinguishers, and a single setting point should have no more than 5. For the company-wide version of the same rules, see Company Fire Equipment Checklist by Area.
Mall sales-floor fire compartments also have rules: under GB 50016-2014 (2018 edition), Code for Fire Protection Design of Buildings, where a shop sales floor in a building of fire-resistance class 1 or 2 is fitted with an automatic fire-extinguishing system and an automatic fire alarm system and uses non-combustible or flame-retardant decoration materials, the maximum permitted floor area of each fire compartment is: no more than 4,000 m² when located in a high-rise building, no more than 10,000 m² when located in a single-storey building or only on the ground floor of a multi-storey building, and no more than 2,000 m² when located underground or semi-underground.
Sales Floor: Extinguishers and Evacuation Signs Are the Priority
The sales floor is the mall's largest area and the most crowded, and its configuration priorities are twofold: extinguishers and evacuation signs.
Extinguishers are mainly ABC dry powder, placed along evacuation routes, at stairwell entrances and near cashier desks. A portable extinguisher's top should be no more than 1.50 m above the floor and its bottom no less than 0.08 m above the floor; it should sit in an extinguisher cabinet or on a hook or bracket, and the cabinet must not be locked.
Evacuation signs and emergency lighting are the top priority in mall configuration: exit signs are fitted above exit doors, directional signs are fitted in evacuation routes to show the way out, and emergency lights ensure corridors and stairwells stay bright enough after a power cut. The lamps follow GB 17945-2024, and the emergency duration follows GB 51309-2018: generally no less than 0.5 hours, and no less than 1 hour for public buildings with a total floor area over 100,000 m². For evacuation lighting in general, see Emergency Lighting and Evacuation Signs.
Catering Area: The Kitchen Is a Class F Fire Place
The mall catering area is a frequent fire location, and a kitchen oil-pan fire is a Class F fire (a fire in cooking oil inside cooking appliances) — its extinguishing method is completely different from other fires: never pour water on a burning oil pan, as water meeting hot oil causes an explosion-like burst, throwing burning oil everywhere.
The catering-area configuration list: each kitchen workspace gets a fire blanket and an ABC dry powder extinguisher, with the blanket hung where it is handy and visible; gas stoves, ovens and other electrical equipment get a carbon dioxide or dry powder extinguisher nearby; and oil fume ducts and exhaust hoods are cleaned regularly, since built-up grease is a common cause of kitchen fires.
Warehouse, Machine Room and Electrical Room: Each Has Its Own Way
A mall warehouse storing goods and packaging materials is a medium-risk Class A fire place, equipped with ABC dry powder extinguishers. Keep a fire lane clear inside the warehouse, and do not let goods block hydrant cabinets or extinguisher setting points. Each fire compartment of a warehouse is calculated separately for configuration numbers.
Machine rooms (fire control rooms, weak-current equipment rooms) get carbon dioxide or clean-gas extinguishers — never water-type or foam extinguishers, to avoid damaging equipment. An electrical room is a Class E fire place, equipped with carbon dioxide or dry powder extinguishers, with a "No Smoking or Open Flames" sign at the door and no combustible clutter stored inside.
Check Frequency: Stricter for Malls Than for Ordinary Units
Mall extinguishers are checked every half month, stricter than the monthly check for ordinary units, under GB 50444-2008, Code for Acceptance and Inspection of Extinguisher Distribution in Buildings: extinguishers in waiting rooms (for trains, planes and ships), song-and-dance entertainment and video-game venues and other crowded public places, as well as yards, tank areas, petrochemical installations, petrol stations, boiler rooms, basements and similar places, are checked every half month. Emergency lighting and evacuation sign lamps are tested monthly for power-switching function, and fire hoses, nozzles and couplings are checked monthly for completeness. Every check must be recorded and kept on file for inspection.
Frequently Asked Questions
How often are mall fire extinguishers checked?
Every half month. A mall is a crowded public place, so under GB 50444-2008 the check frequency is stricter than the monthly check for ordinary units.
What risk level are mall sales floors equipped to?
Generally a medium-risk Class A fire place, with a minimum single-extinguisher rating of 2A and a maximum protected area of 75 m²/A. Follow the fire design documents in each case.
Why does a mall kitchen need a fire blanket?
A kitchen oil-pan fire is a Class F fire and must not be doused with water. A fire blanket laid over the pan cuts off the air and is the simplest, most effective way to put out a starting oil-pan fire, used together with an ABC dry powder extinguisher.
What should a mall watch for in fire equipment during renovation?
Three points: extinguishers and hydrants must not be hidden behind shelves or decoration; exit signs and emergency lights must not be hidden by ceilings or advertising boards; and hot work during renovation needs a hot-work permit, with extinguishers on site and a dedicated watcher.