Category: Firefighting Equipment

How to Maintain Fire Hoses: Drying & Storage

A fire hose is the main line that carries water from a hydrant system. It sits coiled in a hydrant cabinet, unnoticed, until a fire — when it must unroll at once and hold pressure. Poor maintenance means a mouldy lining, an aged woven layer and a leaking coupling, and the hose fails at the critical moment. The maintenance rules are not rules of thumb — they are written into the standard itself.

Know the Standard First: GB 6246-2011, "Fire Hose"

The product standard for fire hoses is GB 6246-2011, Fire Hose, published 30 December 2011 and in force from 1 June 2012, replacing GB 6246-2001, Performance Requirements and Test Methods for Lined Fire Hose, and GB 4580-1984, Unlined Fire Hose. Chapters 3, 4 and 6 and clause 7.1.1 of the standard are mandatory, and the rest are recommended.

Chapter 7 of the standard is devoted to the use and maintenance of hoses — the maintenance requirements are standard content, not rules of thumb. Write the standard number in full and correctly on purchase contracts and acceptance sheets.

A hose's model and specification are made up of design working pressure, nominal inner diameter, length, the woven layer's warp and weft material, and the lining material. A common specification such as "13-65-20" means a design working pressure of 1.3 MPa, a nominal inner diameter of 65 mm and a length of 20 m; "10-65-25" means 1.0 MPa, 65 mm and 25 m. When buying, confirm the model matches the hydrant system's working pressure — a hose whose working pressure is too low may burst on a high-pressure system.

Hoses fall into two types, lined fire hoses and fire wet hoses; lined hoses are the common ones, including rubber hoses, polyurethane (TPU) hoses and polyester glue-filled hoses. Polyurethane hoses are light and wear-resistant, rubber hoses are pressure-resistant, and the choice follows the use scene. For how to choose a hose, see How to Choose a Fire Hose: Size, Length & Material.

After Use: Cleaning, Drying, Inspection

Handling a hose after use has three steps — cleaning, drying and inspection — and none may be skipped.

  • Cleaning: clean the hose after use. A hose that has carried foam must be scrubbed carefully to protect the adhesive layer; a hose soiled with grease can be washed with warm water or soap; a frozen hose must be thawed before cleaning. When cleaning, do not scrape the lining with hard objects — a damaged lining leaks.
  • Drying: a cleaned hose must be dried before storage — a hose that has not been dried must not be rolled up and stored. Dry it hung in a ventilated, shaded place, away from direct sunlight, which speeds ageing of the woven layer and lining. An unlined hose should be hung to dry, then coiled and kept in a cool, dry place.
  • Inspection: while drying, inspect the hose's appearance — the woven layer for damage, skipped threads and scratches; the lining for peeling, blistering and cracking; and the couplings for deformation and aged sealing rings. Repair or replace a problem hose promptly — do not put a faulty hose back into stock.

Storage: Coiled in a Single Layer, Turned Regularly

For long-term storage, a spare hose should be kept in a place of suitable temperature with ventilation, in a dedicated storage spot or store room. Storage method: the hose should be coiled in a single layer and stood upright on a hose rack, turned over twice a year or with the fold edge swapped once. A hose left in one position for a long time ages and cracks at the fold — regular turning extends its service life.

When storing, note: the hose must not touch corrosive chemicals such as oil, acid or alkali; must not be piled on a damp floor; and must not be crushed by heavy objects. A hose in a hydrant cabinet should be coiled as required, avoiding sudden sharp bends, which reduce the hose's pressure resistance.

Hoses carried on vehicles (fire engines and mini fire stations) should be kept from rubbing against each other, swapping the fold edge where needed. After every call-out, handle them by the cleaning, drying and inspection routine — never stuff a used hose straight back into the vehicle.

Use: Laying, Water Supply, Frost Protection

When laying a hose, avoid sharp objects and all kinds of oil; when laying vertically to height, use hose hooks; when laying across a road, lay a hose bridge over it; when laying across a railway, run the hose under the track so wheels do not crush it and cut off the water supply.

When laying, avoid sudden sharp bends and twisting. After filling with water, do not drag the hose forcefully on the ground — to move it, lift it as much as possible to reduce wear against the ground. After filling, a hose turning may pull an internal-snap coupling apart, so make sure the coupling connection is firm when laying.

In severe winter, when water supply must pause at a fire scene, keep the pump running slowly with a small discharge to stop the hose freezing. In cold regions, use lined hoses when laying outside buildings. A frozen hose must not be bent forcefully — thaw it first. For how to work out how many extinguishers a place needs, see How to Configure Fire Extinguishers: Place, Quantity and Inspection, and for home extinguisher choice, see How to Choose a Home Fire Extinguisher.

Frequently Asked Questions

How often should a hose be checked?

Check the appearance once a month — damage, mould, and whether the couplings are intact. Sample-test pressure resistance once a quarter, and run a water pressure test where possible. Turn stored hoses over or swap the fold edge twice a year.

What happens if a hose is put away without drying?

Damp storage easily breeds mould, and the woven layer and lining age and turn brittle faster, so the hose may leak or even burst at the next use. A hose that has not been dried must not be rolled up and stored — that is an explicit requirement in the standard.

What does the hose model 13-65-20 mean?

13 is the design working pressure, 1.3 MPa; 65 is the nominal inner diameter, 65 mm; 20 is the length, 20 m. When buying, confirm the working pressure matches the hydrant system.

What should I do if a hose coupling leaks?

First check whether the sealing ring is aged or damaged, and replace an aged ring promptly; then check whether the coupling is deformed or the joint between the coupling and the hose is loose. Replace a damaged coupling as a whole — do not make do.

WhatsApp 18300232331 Get a Free Quote
Chat Get a Quote