How to Choose Fire Hydrants: Indoor vs Outdoor Types
Fire hydrants come in two main types — indoor and outdoor — with different standards, structures and installation methods. An indoor hydrant sits in a hydrant cabinet for people to draw water and fight a fire nearby; an outdoor hydrant stands outside a building for fire engines to draw water or discharge directly. When buying, first work out where it will be used, then match the model.
Indoor Hydrants: GB 3445-2018, SN65 the Most Common
Indoor hydrants follow GB 3445-2018, Indoor Fire Hydrants. The most common model is SN65, where SN stands for indoor fire hydrant and 65 for the nominal bore DN65. The SN65 inlet pipe thread is G2 — a 2-inch pipe thread — and the outlet is an internal snap-type DN65 fire coupling, which connects directly to a 65-type fire hose. The nominal pressure is commonly 1.6 MPa.
Indoor hydrants are divided by outlet form into single-outlet and double-outlet, by number of valves into single-valve and double-valve, and by structure into right-angle outlet, 45-degree outlet, rotary, pressure-reducing, rotary pressure-reducing, pressure-reducing and stabilising, rotary pressure-reducing and stabilising, and reducing tee types. In the low zone of a high-rise building, where water pressure is too high, choose a pressure-reducing or pressure-reducing and stabilising type — otherwise the outlet pressure is too high and the hose and nozzle are hard to control.
An indoor hydrant is generally installed in a hydrant cabinet, with a hose, nozzle, hose reel and similar equipment. Hydrant cabinets follow GB/T 14561-2019, Fire Hydrant Cabinets — when buying, check the cabinet size against the hydrant body and the coiled hose together, since a cabinet that cannot fit them or whose door will not close is a common cause of rework.
Outdoor Hydrants: GB 4452-2011, Above Ground and Underground
Outdoor hydrants follow GB 4452-2011, Outdoor Fire Hydrants. By installation they are divided into above-ground (SS), underground (SA) and folding (SD) types; by inlet connection into flange and socket types; by inlet nominal bore into 100 mm and 150 mm; and by nominal pressure into 1.0 MPa (socket type) and 1.6 MPa (flange type).
An above-ground outdoor hydrant stands out of the ground and is easy to use, but in cold northern regions choose a model with a frost-proof drain device — otherwise water left in the hydrant will freeze in winter and crack the valve body. An underground type is buried, with only the cover showing, so it does not affect the road or the landscape — but drawing water means opening the cover and connecting a suction pipe, which is slower. Special types include foam, anti-collision, pressure-regulating and pressure-reducing and stabilising models, chosen by place.
An outdoor hydrant must match the municipal water supply network's pipe diameter and pressure — whether the inlet is 100 mm or 150 mm, flange or socket, must follow the design drawings, not price alone.
Matching Parts: Hydrant, Hose and Nozzle as a Set
The usual matching set for an indoor hydrant is: one 65-type fire hose, 20 m or 25 m long; one straight-stream nozzle with a DN65 coupling; and a hose-reel nozzle where a fire hose reel is fitted. Coupling sizes must be uniform — with a DN65 hydrant outlet, the hose, nozzle and couplings are all 65-type, and a 50-type part mixed in will not connect.
When buying, check the coupling form: an indoor hydrant outlet is an internal snap-type coupling, so both ends of the hose need internal snap-type couplings; an outdoor hydrant outlet may be threaded or snap-type, and must match the fire brigade's water-drawing equipment. Small accessories such as seals and blank caps must also be complete — one missing seal and the coupling leaks.
Acceptance and Maintenance: A Discharge Test Every Year
Accept a hydrant on delivery on three points: whether the product standard is correct — GB 3445-2018 for indoor hydrants, GB 4452-2011 for outdoor hydrants; whether the fire product certification certificate is valid, with the certificate number, model and producer all matching; and appearance — no casting defects, a handwheel that turns freely, and a valve stem that rises and falls smoothly.
After commissioning, maintain them regularly. Indoor hydrants should have a discharge test every year at the most unfavourable point and the highest-pressure point; outdoor hydrants should have a discharge test every year, one by one. Daily checks include: whether the hydrant cabinet door is blocked, whether the equipment inside the cabinet is complete, whether the hose is mouldy, whether the nozzle sealing washer is intact, and whether outdoor hydrants are buried or damaged. Fix problems promptly — do not wait for a fire to discover a hydrant will not open. For the matching extinguishers, see how to configure fire extinguishers and extinguisher inspection and scrapping rules.
Frequently Asked Questions
What is the difference between SN65 and SN50?
The core difference is the nominal bore: SN65 is DN65, SN50 is DN50. The SN65 inlet pipe thread is G2, the SN50 is G1.5, and the matching pipes and hoses differ in bore accordingly. Indoor hydrants are mainly SN65; SN50 is used more in special places.
Can an indoor fire hydrant be installed outdoors?
No. An indoor hydrant has no frost or impact protection — installed outdoors it will freeze and crack in winter, and it does not meet the design code. Use outdoor hydrants outdoors and indoor hydrants indoors — do not mix them.
Why do high-rise buildings need pressure-reducing hydrants?
In the low zone of a high-rise building, the static water pressure at a hydrant can exceed 1.0 MPa, and too high an outlet pressure can burst hoses and make nozzles hard to hold. A pressure-reducing or pressure-reducing and stabilising hydrant keeps the outlet pressure within a reasonable range.
Must a hydrant cabinet contain a hose and a nozzle?
Under the design code, a hydrant cabinet should contain a hose, a nozzle and similar equipment. Missing equipment in a cabinet is a failure at acceptance, and missing items found in daily checks must be topped up promptly.